How to Calculate Amps from Watts on a 3-Phase Circuit
See the three-phase formula for turning watts into amps, with a worked example and the role of line voltage and power factor in shop loads.
Contents
- Volts and power factor in the formula
- Worked example with real numbers
- Using a calculator and totaling shop loads
- Questions about 3-phase amps and watts
- Why do you multiply by 1.732 for 3-phase?
- Is line current the same as phase current?
- What power factor should I use if I don't know it?
- Can I use the single-phase formula on a 3-phase circuit?
To calculate amps from watts on a 3-phase circuit, divide watts by volts times 1.732 times power factor. The figure 1.732 is the square root of 3, the factor that links line voltage to three-phase power. Below are the three phase formula, a worked example and notes for a shop 3-phase supply.
Volts and power factor in the formula
Calculating amps from watts and volts on 3 phase requires the line voltage and the power factor. Line voltage is the voltage measured between any two of the three hot conductors. Power factor, the ratio of real power to apparent power, ranges from 0 to 1. Heaters and other resistive loads sit close to 1, while motor-driven tools such as compressors run lower.
Worked example with real numbers
A 3-phase load of 10,000 watts on 400 volts at power factor 1 draws about 14.4 amps. First multiply 1.732 by 400 to get 692.8, then divide 10,000 by that figure. With a power factor of 0.8, the same load draws about 18 amps instead. The result is line current, the current flowing in each supply wire.
Using a calculator and totaling shop loads
A watts to amps calculator for 3 phase applies the same formula to the numbers you enter. Pick a calculator that asks for power factor, since leaving it at 1 understates motor current. For a full shop, convert each 3-phase tool to amps and add the tools that run together. Breaker and wire sizing from that total is work for a qualified electrician.
Questions about 3-phase amps and watts
Why do you multiply by 1.732 for 3-phase?
The 1.732 factor in 3-phase math is the square root of 3. In a wye, or star, connection, line voltage equals phase voltage times 1.732. The factor lets three-phase power be expressed with line voltage and line current alone.
Is line current the same as phase current?
Line current equals phase current in a wye connection but not in a delta connection. In a delta connection, line current is phase current times 1.732. The watts-to-amps formula gives line current, which is the figure used for wire and breaker sizing.
What power factor should I use if I don't know it?
Check the tool nameplate first, since power factor is often printed there as PF or cos phi. Motor nameplates also list rated amps, which removes the need to calculate current. Using 1 for a motor gives a lower amp figure than the tool actually draws. Where no figure is available, ask the manufacturer or an electrician for the rated value.
Can I use the single-phase formula on a 3-phase circuit?
No, the single-phase formula overstates current on a 3-phase circuit because it leaves out 1.732. Single-phase current is watts divided by volts times power factor. On three phases, the load spreads across three wires, so each line carries less current.